What are the installation instructions and requirements?

Lightning and surge protection may only be installed, put into operation and maintained by qualified electricians who are familiar with national and international laws, regulations and standards. Among other things, normative requirements regarding line lengths, effective protection areas and fuse protection of surge protection devices must be observed.

Areas of application

Control cabinet Electrical installation

Surge protection devices are always installed where cables are fed into the control cabinet. This prevents interference from being coupled into the control cabinet. They are diverted directly at the beginning of the control cabinet.

Type I lightning arrester

As a general rule, a surge protection device should be installed as close as possible to the power supply point of the electrical system. The insert of the appropriate SPD shall ensure voltage limitation in accordance with the insulation coordination. This protects the downstream installation equipment.

  • These powerful interference pulses are dissipated to the earth via type I lightning current arresters directly on the feed-in or the main distribution and limited to voltages below 6 kV.
  • Type I arresters must be installed before or after the electricity meter as soon as the building has external lightning protection or an overhead line feed.
  • Only leakage current free arresters (LCF = Leakage current free) are permitted upstream of the electricity meter.

Type II surge protection arresters

The insulation strength from the main distribution board up to and including the sub-distribution board is 4 kV. The surge arrester (type II) is normally installed in the sub-distribution board and then limits the voltage to below 4 kV.

  • Type II arresters are installed in the main distribution board if the building has no external lightning protection and no overhead line feed. In this case, installation is only permitted after the electricity meter.

Type III surge protection arresters

The insulation strength from the sub-distribution board to the end device is 2.5 kV. The end device surge protection (type III) is ultimately located directly in front of the device to be protected and limits the voltage to below 2.5 kV.

  • There are DIN rail solutions as well as products that can be installed directly behind the socket in the cable conduit.

Line connection and installation

Line connection Surge protection

All SPDs have an earth-connection terminal point. The earthing wire for the associated equipotential bonding rail must be connected to this point. The earthing wire must be as short as possible with the largest possible cross-section, since each centimetre of line length increases the residual voltage of the SPD.

  • Rule of thumb: 1 m cable = 1 kV voltage drop

In type I arresters, both earth-connection terminals must be connected. One cable leads to the equipotential bonding connection on the building and the second cable is connected to the PE conductor on the installation.

Cable lengths

Cable lengths

Due to the inductive conductor resistant, a transient voltage surge can quickly cause a voltage drop of multiple 1,000 V. This would degrade the effective protection level of a SPD so far that the voltage resistance of the installation or the device to be protected could be exceeded despite the use of an SPD. In the worst case scenario, the device could be damaged, destroyed or a fire could even be started.

  • For this reason, the standard requires a maximum cable length of ≤ 0.5 m for the connecting lines of an SPD.
  • The installation can be realised using the so-called V-connection or a single branch wiring.

V wiring

  • V wiring

The incoming and outgoing cables are connected directly to the terminals of the SPD. This results in a V-shaped connection geometry. This method minimises line lengths and reduces additional voltages and contact resistances.

Single branch wiring

  • Single branch wiring

A cable is branched off from the main circuit and connected directly to the surge protection device. This results in a T-shaped connection geometry. Wiring may cause higher interference because the line length is greater and additional contact resistance may occur.

Protected area

Line length protected area

To ensure effective protection, the surge protection must be installed as close as possible to the feed point for the electrical system. For a residential building, for example, this is directly at the mains infeed in the bottom connection area of the meter cabinet.

Potential intrinsic sources of interference within the building must also be taken into consideration. In these cases, the surge protection also needs to be installed as close as possible to the triggering device.

Line length protected area

The standard (VDE 0100-534) regulates the maximum distance between a surge protection device and the devices to be protected (effective protection range).

  • The length of the cables should be ≤ 10 m (see figure above).
  • If this distance cannot be maintained, an additional surge protection device must be installed as close as possible to the device to be protected.

Line cross-sections

Line cross-sections

As a rule, the same cable cross-section is selected for the connecting cables to the SPD as for the outer conductor (L1, L2, L3) and the neutral conductor (N).

The standards IEC 603640100-534 (VDE 0100-534) require the minimum cable cross-sections shown in the table for type I and type II SPDs.

TypeConnecting lines between SPD and line conductorConnecting lines between SPD and main grounding busbar or protective earth (PE or PEN)
I6 mm2 Cu (copper)16 mm2 Cu(copper)
II2.5 mm2 Cu(copper)6 mm2 Cu(copper)

For safety reasons, SPDs are protected against short circuits or overloads by means of an overcurrent protection element (F2) designed for the type of installation and the cross-section of the connected cable.

The cable cross-sections and backup protection for surge protection devices with a short-circuit resistance (Isccr) of 50 kA and 25 kA are shown in the table as examples.

Fuse protection for surge protection devices

Wiring diagram for fuse of a surge protection device

In normal operation, SPDs act as passive, non-conductive components. A flow of current occurs only in the case of a surge voltage or at the end of the service life for the protective components. For this purpose, the SPDs are protected against short circuits or overloads by means of an overcurrent protection element (F2).

  • Additional protection (F2) is only needed if the nominal value of the fuse F1 on the system side is greater than the maximum current of the SPD specified by the manufacturer.
  • Fuses and circuit breakers can be used.
  • Alternatively, surge protection with an integrated fuse can be installed.

Fuses rated currents

  • Fuses have a melting device that unbinds the connection and interrupts the electric circuit in the event of overload.
  • Fuses are single-use components and must be replaced after tripping.
  • The figure shows the behaviour of fuses with a lightning impulse current of 10/350 μs. The lightning current carrying capacity is severely limited, especially with small fuses.
  • The fuses must be chosen taking into account the rated currents specified for the SPD. It must be ensured that the line protection (F2) is actually capable of carrying lightning currents and that the maximum back-up fuse is selected for the dimensioning.

  • Circuit breakers (LS switches for short) provide overload protection through a thermal initiator and protection against short circuits through electromagnetic tripping.
  • They can be switched on again after initiation and are therefore reusable.
  • If circuit breakers are inserted, the values (Icu) or (Icn) must be large enough to carry the lightning/discharge current (like gG fuse), i.e. greater than Iimp.
  • You can find more information on circuit-breakers in our application note under Downloads.

VPU AC I with integrated fuse

  • An additional fuse (F2) needs space and longer connecting lines. A reliable alternative is surge protection with an integrated fuse.
  • Planning and installation are simplified because no additional back-up fuse (F2) is required upstream of the surge protection device, regardless of the main fuse rating F1 (even greater than 315 A).
  • The VPU AC F series monitors the status of the fuse and the SPD.

Downloads

Consulting & Support

Do you have questions about our products and services or would you like an individual offer? Simply fill out contact form. Our employees will contact you as soon as possible.

* Required fields